Taco 0011 High Velocity Cartridge Circulator – 1/8 HP for High-Head Hydronic Applications
The Taco 0011 is a high-performance circulator designed for closed-loop hydronic heating and chilled water systems where medium flow and high head are required. Common applications include fan coil units, heat exchangers, and high-pressure drop boilers. With its 1/8 HP motor and precision hydraulic design, the 0011 provides dependable flow across demanding system profiles.
This model features Taco’s replaceable cartridge design, which houses all moving parts in a self-contained module, simplifying maintenance and extending pump service life. Its quiet, self-lubricating operation and flange-to-flange compatibility make it a reliable upgrade or replacement for legacy installations.
Product Highlights
- High Head, Medium FlowDesigned for applications up to 31 feet of head and flow rates approaching 31 GPM.
- Field-Serviceable CartridgeReplaceable cartridge contains all moving components, reducing downtime during maintenance.
- Quiet OperationPermanent split capacitor motor runs quietly and efficiently in both heating and cooling systems.
- Durable Housing OptionsAvailable in cast iron for closed-loop systems and bronze for open-loop or domestic water applications.
- Self-Lubricating DesignEliminates the need for oiling or additional lubrication service intervals.
- Standard Flange DimensionsCompatible with most existing 0011 installations and competitive models for easy retrofit.
Technical Specifications
- ModelTaco 0011-F
- Horsepower1/8 HP
- Voltage115V, 60 Hz
- Maximum Flow31 GPM
- Shutoff Head31 feet
- Maximum Operating Pressure150 PSI
- Temperature Range40°F to 230°F
- Dimensions7.5″ Depth x 5.625″ Width x 6.5″ Height
Installation Considerations
Designed for flange mounting, the 0011 circulator should be installed with consideration for system pressure and temperature requirements. Isolation valves are recommended for service access. Ensure compliance with local plumbing and mechanical codes. Wiring should be performed by qualified personnel to ensure proper voltage and grounding.
Contractor Notes
- Use cast iron models for closed-loop systems; use bronze in potable water or open-loop applications.
- Check pump curve against system head loss to verify proper selection.
- Install with arrow pointing in direction of flow; prime system before startup.
Specifications
Buying Information
Verify model 0011-F4 and the listed specifications match your application before ordering.